NAP-50A is a miniature & low power consumption type of NAP-2A, and is mainly used for gas detectors. Compared to NAP-55A, NAP-50A has a lower alcohol sensitivity to eliminate false alarms caused by alcohol, thus more reliable gas detectors can be produced with NAP-50A. The following are the basic characteristics but it is recommended to refer to the individual userfs manual for further information. See NAP-2A for measuring circuit for sensor evaluation.


Structure & Appearance of NAP-50A

Target gases and detection range

Gases Detection range
Methane CH4 0.05 ~ 5% (0.05 ~ 2%)
Ethane C2H6 0.05 ~ 3.2“ (0.05 ~ 1.5“)
Iso-butane Iso-C4H10 0.03 ~ 1.8“ (0.03 ~ 0.8“)
Hydrogen H2 0.05 ~ 4“ (0.05 ~ 1.5“)
Hydrocarbons CnH2n+2 1~100% LEL (1~50%LEL)

(@) is a detection range in high accuracy


Ratings

Items Specifications
Supply voltage DC 2.5 +/- 0.25V
AC 2.5 +/- 0.25V (r.m.s. 50~60Hz)
Current (When 2.5V is applied) DC 150 ~ 170mA
AC 150 ~ 170mA (r.m.s. 50~60Hz)
Ambient Temperature In operation -10 ~ +50Ž
In storage -10 ~ +50Ž
Ambient humidity In operation 95“RH or less
In operation 99“RH or less(No dew condensation)

Gas sensitivity characteristics

Gases & concentration Output voltage
Output in air -35 ~ +35mV
Methane 3000ppm 10 ~ 16mV
Iso-butane 1400ppm 9 ~ 14mV
Hydrogen 1400ppm 7 ~ 12mV
Ethanol 1% Less than 10mV

Gas sensitivity characteristics Response characteristics