Various sensor products
NIS-5A
NIS-05A is also an ionization type smoke sensor. The radioisotope 241Am is used as the radiation source, but the radioactivity is about 55% of NIS-09C and the whole sensor is covered with metallic housing which eliminates the fear of radiation leakage. The pin location and the performances are compatible to sensors produced by other manufacturer than Nemoto.
 |
| Structure |
Ratings
| Items |
Characteristics |
| Supply voltage |
Less than DC 6 ~ 12V |
| Supply voltage |
15 } 3pA |
| Radiation source |
Americium-241, 18.5KBq |
| Ambient Temp. |
0 ~ 50oC |
| Ambient humidity |
Less than 95“RH |
Characteristics
| Item |
Characteristics |
| Output in clean air |
5.5 } 0.5V |
Smoke sensitivity
2“/foot Cotton thread |
1.2 } 0.3V |
Remarks) The IC appeared in the above circuit, MC14466 may not be on the market any more. Compatible ICs will be MC14468, A5367, and A5368 etc.